Studying the Thermal Characteristics of a Copper Loop Heat Pipe with a Flat Evaporator
Аннотация
Abstract— The article presents the results of experiments aimed at studying the thermal characteristics of a copper loop heat pipe (LHP) with a newly designed flat evaporator and a U-shaped tubular condenser. Water and methanol were used as working fluids. The tests were carried out on the horizontally oriented device with heat sources that had the heating surface areas equal to 25 and 35 cm 2 . The flowrate of thermostatically controlled condenser cooling water was equal to 3.6 dm 3 /min, and its temperature at the inlet was equal to 20 and 40°С. The minimum thermal resistance of the evaporator with water equal to 0.017 °С/W was achieved when using the heat source with an area of 35 cm 2 at a heat load equal to 600 W, which was limited only by the heater power. The temperature on the heat source heating surface was in that case equal to 79.5°С. The minimum thermal resistance of the evaporator with methanol was equal to 0.019°С/W at the heat load equal to 300 W and heat source temperature equal to 86.4°С. The minimum thermal resistance of the evaporator with water and the heat source with an area of 25 cm 2 was equal to 0.024°С/W at the heat load equal to 900 and temperature equal to 105.7°С. In the case of using methanol, the following values were obtained: 0.022°С/W at 300 W and heat source temperature equal to 86.4°С. The results of the presented LHP development and study results may be used, in particular, in designing the cooling systems of the functional components of powerful electronic devices, such as e.g. central and graphics processors used in the computer servers installed at data centers.